Life Safety and Fire Fighting Systems – The weakest hyperlink

Unlike different cables, fire resistant cables should work even when instantly uncovered to the hearth to maintain important Life Safety and Fire Fighting tools working: Fire alarms, Emergency Lighting, Emergency Communication, Fire Sprinkler pumps, Fireman’s Lift sub-main, Smoke extraction fans, Smoke dampers, Stair pressurization followers, Emergency Generator circuits etc.
In order to categorise electrical cables as hearth resistant they are required to undergo testing and certification. Perhaps the first frequent hearth checks on cables were IEC 331: 1970 and later BS6387:1983 which adopted a fuel ribbon burner test to provide a flame in which cables had been placed.
Since the revision of BS6387 in 1994 there have been eleven enhancements, revisions or new check requirements launched by British Standards to be used and software of Fire Resistant cables but none of these seem to handle the core problem that fire resistant cables the place tested to common British and IEC flame test requirements aren’t required to carry out to the identical fireplace performance time-temperature profiles as each different structure, system or element in a constructing. Specifically, the place fireplace resistant buildings, methods, partitions, fireplace doorways, fireplace penetrations fireplace obstacles, flooring, partitions etc. are required to be fireplace rated by constructing regulations, they’re examined to the Standard Time Temperature protocol of BS476 elements 20 to 23 (also often recognized as ISO834-1, ASNZS1530pt4, EN1363-1 and in America and Canada ASTM E119-75).
These exams are performed in large furnaces to duplicate real post flashover fire environments. Interestingly, Fire Resistant cable take a look at standards like BS 6387CWZ, SS299, IEC 60331 BS8343-1 and a pair of, BS8491 only require cables to be uncovered to a flame in air and to decrease ultimate check temperatures (than required by BS476 pts 20 to 23). Given Fire Resistant cables are more likely to be uncovered in the identical fireplace, and are wanted to ensure all Life Safety and Fire Fighting systems stay operational, this truth is maybe surprising.
Contrastingly in Germany, Belgium, Australia, New Zealand, USA and Canada Fire Resistant cable systems are required to be examined to the same fireplace Time Temperature protocol as all other constructing parts and this is the Standard Time Temperature protocol to BS476pts 20-23, IS0 834-1, EN1363-1 or ASTM E119-75 in USA.
The committees developing the standard drew on the guidance given from the International Fire Prevention Congress held in London in July 1903 and the measurements of furnace temperatures made in many hearth exams carried out within the UK, Germany and the United States. The exams were described in a sequence of “Red Books” issued by the British Fire Prevention Committee after 1903 in addition to these from the German Royal Technical Research Laboratory. The finalization of the ASTM commonplace was closely influenced by Professor I.H. Woolson, a Consulting Engineer of the USA National Board of Fire Underwriters and Chairman of the NFPA committee in Fire Resistive Construction who had carried out many checks at Columbia University and Underwriters Laboratories in Chicago. The small time temperature differences between the International ISO 834-1 check as we know it right now and the America ASTM E119 / NFPA 251 exams probably stemmed from this time.
Image courtesy of MICC Ltd.
The curve as we see it today (see graph above) has turn out to be the standard scale for measurement of fireside take a look at severity and has proved relevant for many above floor cellulosic buildings. When components, structures, elements or systems are tested, the furnace temperatures are managed to conform to the curve with a set allowable variance and consideration for initial ambient temperatures. The requirements require components to be tested in full scale and underneath conditions of help and loading as defined to have the ability to characterize as precisely as potential its functions in service.
This Standard Time Temperature testing protocol (see graph right) is adopted by virtually all international locations all over the world for hearth testing and certification of nearly all constructing structures, components, systems and parts with the interesting exception of fire resistant cables (exception in USA, Canada, Australia, Germany, Belgium and New Zealand the place hearth resistant cable systems are required to be tested and permitted to the Standard Time Temperature protocol, identical to all other building structures, elements and components).
It is important to know that software requirements from BS, IEC, ASNZS, DIN, UL and so on. the place fireplace resistive cables are specified to be used, are only ‘minimum’ requirements. We know today that fires aren’t all the identical and research by Universities, Institutions and Authorities around the globe have recognized that Underground and a few Industrial environments can exhibit very completely different fire profiles to those in above floor cellulosic buildings. Specifically in confined underground public areas like Road and Rail Tunnels, Underground Shopping facilities, Car Parks fireplace temperatures can exhibit a very quick rise time and might attain temperatures well above these in above floor buildings and in far less time. In USA today electrical wiring techniques are required by NFPA 502 (Road Tunnels, Bridges and different Limited Access Highways) to face up to fire temperatures up to 1,350 Degrees C for 60 minutes and UK British Standard BS8519:2010 clearly identifies underground public areas corresponding to car parks as “Areas of Special Risk” the place extra stringent check protocols for essential electric cable circuits might have to be thought-about by designers.
Standard Time Temperature curves (Europe and America) plotted in opposition to frequent BS and IEC cable tests.
Of course all underground environments whether or not street, rail and pedestrian tunnels, or underground public environments like shopping precincts, car parks and so forth. could exhibit different fire profiles to these in above floor buildings because In these environments the heat generated by any hearth can’t escape as easily as it would in above floor buildings thus relying extra on heat and smoke extraction tools.
For Metros Road and Rail Tunnels, Hospitals, Health care amenities, Underground public environments like buying precincts, Very High Rise, Theaters, Public Halls, Government buildings, Airports and so on. this is notably essential. pressure gauge น้ำมัน of those public environments is commonly slow even throughout emergencies, and it’s our duty to make sure everyone is given the easiest probability of safe egress during fire emergencies.
It can be understood today that copper Fire Resistant cables the place put in in galvanized metal conduit can fail prematurely during fireplace emergency due to a response between the copper conductors and zinc galvanizing contained in the metal conduit. In 2012 United Laboratories (UL®) in America removed all certification for Fire Resistive cables the place installed in galvanized steel conduit for this reason:
UL® Quote: “A concern was dropped at our consideration related to the efficiency of these merchandise in the presence of zinc. We validated this discovering. As a result of this, we modified our Guide Information to indicate that each one conduit and conduit fittings that come in contact with hearth resistive cables should have an inside coating free of zinc”.
Time temperature profile of tunnel fires utilizing vehicles, HGV trailers with totally different cargo and rail carriages. Graph extract: Haukur Ingason and Anders Lonnermark of the Swedish National Testing and Research Institute who offered the paper on the First International Symposium in Prague 2004: Safe and Reliable Tunnels.
It would appear that some Standards authorities all over the world may need to evaluation the present test methodology at present adopted for fireplace resistive cable testing and perhaps align the efficiency of Life Safety and Fire Fighting wiring methods with that of all the opposite fire resistant constructions, elements and techniques so that Architects, building designers and engineers know that once they want a hearth rating that the important wiring system might be equally rated.
For many power, control, communication and data circuits there is one expertise out there which can meet and surpass all present fire exams and applications. It is an answer which is frequently used in demanding public buildings and has been employed reliably for over 80 years. MICC cable expertise can provide a total and full reply to all the problems associated with the fire security dangers of recent flexible natural polymer cables.
The metal jacket, magnesium oxide insulation and conductors of MICC cables make positive the cable is successfully fireplace proof. Bare MICC cables have no natural content so simply cannot propagate flame or generate any smoke. The zero fuel-load of those MICC cables ensures no warmth is added to the fireplace and no oxygen is consumed. Being inorganic these MICC cables cannot generate any halogen or poisonous gasses at all including Carbon Monoxide. MICC cable designs can meet all the current and constructing hearth resistance performance requirements in all countries and are seeing a significant enhance in use globally.
Many engineers have beforehand thought of MICC cable technology to be “old school’ but with the new research in fire performance MICC cable system at the second are confirmed to have far superior hearth performances than any of the newer more modern flexible fire resistant cables.