Life Safety and Fire Fighting Systems – The weakest hyperlink

Unlike other cables, hearth resistant cables have to work even when directly exposed to the fireplace to maintain essential Life Safety and Fire Fighting gear working: Fire alarms, Emergency Lighting, Emergency Communication, Fire Sprinkler pumps, Fireman’s Lift sub-main, Smoke extraction followers, Smoke dampers, Stair pressurization fans, Emergency Generator circuits and so forth.
In order to classify electrical cables as fireplace resistant they are required to bear testing and certification. Perhaps the first frequent fire tests on cables had been IEC 331: 1970 and later BS6387:1983 which adopted a fuel ribbon burner take a look at to produce a flame in which cables had been placed.
Since the revision of BS6387 in 1994 there have been eleven enhancements, revisions or new test requirements launched by British Standards to be used and application of Fire Resistant cables but none of those seem to deal with the core issue that fireplace resistant cables the place tested to widespread British and IEC flame check requirements usually are not required to carry out to the identical fire performance time-temperature profiles as each other structure, system or element in a constructing. Specifically, where hearth resistant structures, techniques, partitions, fireplace doorways, hearth penetrations hearth limitations, flooring, walls and so forth. are required to be fireplace rated by building regulations, they’re examined to the Standard Time Temperature protocol of BS476 elements 20 to 23 (also generally known as ISO834-1, ASNZS1530pt4, EN1363-1 and in America and Canada ASTM E119-75).
These exams are carried out in large furnaces to duplicate actual publish flashover fireplace environments. Interestingly, Fire Resistant cable test requirements like BS 6387CWZ, SS299, IEC 60331 BS8343-1 and a pair of, BS8491 only require cables to be exposed to a flame in air and to lower final take a look at temperatures (than required by BS476 pts 20 to 23). Given Fire Resistant cables are more probably to be exposed in the same hearth, and are wanted to make sure all Life Safety and Fire Fighting methods remain operational, this fact is probably stunning.
Contrastingly in Germany, Belgium, Australia, New Zealand, USA and Canada Fire Resistant cable methods are required to be examined to the identical hearth Time Temperature protocol as all different building parts and this is the Standard Time Temperature protocol to BS476pts 20-23, IS0 834-1, EN1363-1 or ASTM E119-75 in USA.
The committees creating the standard drew on the steerage given from the International Fire Prevention Congress held in London in July 1903 and the measurements of furnace temperatures made in lots of hearth tests carried out within the UK, Germany and the United States. The tests had been described in a collection of “Red Books” issued by the British Fire Prevention Committee after 1903 in addition to these from the German Royal Technical Research Laboratory. The finalization of the ASTM normal was closely influenced by Professor I.H. Woolson, a Consulting Engineer of the USA National Board of Fire Underwriters and Chairman of the NFPA committee in Fire Resistive Construction who had carried out many tests at Columbia University and Underwriters Laboratories in Chicago. The small time temperature variations between the International ISO 834-1 check as we know it today and the America ASTM E119 / NFPA 251 checks likely stemmed from this time.
Image courtesy of MICC Ltd.
The curve as we see it today (see graph above) has become the usual scale for measurement of fireplace test severity and has proved relevant for many above ground cellulosic buildings. When components, structures, elements or methods are tested, the furnace temperatures are managed to adapt to the curve with a set allowable variance and consideration for preliminary ambient temperatures. The requirements require elements to be examined in full scale and under situations of help and loading as defined to find a way to symbolize as accurately as attainable its functions in service.
This Standard Time Temperature testing protocol (see graph right) is adopted by almost all international locations all over the world for hearth testing and certification of just about all building buildings, elements, systems and elements with the attention-grabbing exception of fireplace resistant cables (exception in USA, Canada, Australia, Germany, Belgium and New Zealand where fireplace resistant cable methods are required to be tested and approved to the Standard Time Temperature protocol, just like all other constructing constructions, elements and components).
It is necessary to know that application requirements from BS, IEC, ASNZS, DIN, UL etc. where hearth resistive cables are specified to be used, are solely ‘minimum’ necessities. We know today that fires are not all the identical and analysis by Universities, Institutions and Authorities all over the world have identified that Underground and some Industrial environments can exhibit very completely different fire profiles to those in above floor cellulosic buildings. Specifically in confined underground public areas like Road and Rail Tunnels, Underground Shopping facilities, Car Parks fire temperatures can exhibit a very fast rise time and can reach temperatures nicely above those in above floor buildings and in far much less time. In USA right now electrical wiring methods are required by NFPA 502 (Road Tunnels, Bridges and different Limited Access Highways) to resist fireplace temperatures as much as 1,350 Degrees C for 60 minutes and UK British Standard BS8519:2010 clearly identifies underground public areas corresponding to automobile parks as “Areas of Special Risk” where extra stringent take a look at protocols for important electric cable circuits may need to be considered by designers.
Standard Time Temperature curves (Europe and America) plotted in opposition to widespread BS and IEC cable tests.
Of course all underground environments whether street, rail and pedestrian tunnels, or underground public environments like purchasing precincts, car parks etc. could exhibit totally different fire profiles to those in above ground buildings as a outcome of In these environments the warmth generated by any fireplace can’t escape as simply as it would in above floor buildings thus relying more on warmth and smoke extraction tools.
For Metros Road and Rail Tunnels, Hospitals, Health care services, Underground public environments like purchasing precincts, Very High Rise, Theaters, Public Halls, Government buildings, Airports and so on. this is significantly important. Evacuation of those public environments is commonly gradual even during emergencies, and it is our duty to ensure everyone is given the easiest chance of safe egress during hearth emergencies.
It is also understood at present that copper Fire Resistant cables the place put in in galvanized metal conduit can fail prematurely throughout fire emergency due to a reaction between the copper conductors and zinc galvanizing inside the steel conduit. In 2012 United Laboratories (UL®) in America removed all certification for Fire Resistive cables the place put in in galvanized metal conduit because of this:
UL® Quote: “A concern was delivered to our consideration related to the efficiency of those products in the presence of zinc. We validated this finding. As a result of this, we changed our Guide Information to point that every one conduit and conduit fittings that are available in contact with fireplace resistive cables ought to have an inside coating free of zinc”.
Time temperature profile of tunnel fires using vehicles, HGV trailers with totally different cargo and rail carriages. Graph extract: Haukur Ingason and Anders Lonnermark of the Swedish National Testing and Research Institute who presented the paper on the First International Symposium in Prague 2004: Safe and Reliable Tunnels.
It would seem that some Standards authorities around the globe might need to evaluate the current take a look at methodology currently adopted for fireplace resistive cable testing and perhaps align the performance of Life Safety and Fire Fighting wiring methods with that of all the opposite fire resistant constructions, parts and systems in order that Architects, constructing designers and engineers know that after they want a hearth score that the essential wiring system might be equally rated.
For many energy, control, communication and data circuits there’s one technology obtainable which can meet and surpass all present hearth tests and applications. It is a solution which is frequently used in demanding public buildings and has been employed reliably for over 80 years. MICC cable expertise can provide a complete and full answer to all the problems associated with the fireplace safety dangers of modern versatile organic polymer cables.
The metallic jacket, magnesium oxide insulation and conductors of MICC cables make positive the cable is effectively fire proof. Bare MICC cables don’t have any organic content material so simply can’t propagate flame or generate any smoke. The zero fuel-load of these MICC cables ensures no warmth is added to the fire and no oxygen is consumed. Being เกจวัดแรงดันแก๊สco2 can’t generate any halogen or toxic gasses in any respect together with Carbon Monoxide. MICC cable designs can meet all of the current and constructing fireplace resistance efficiency requirements in all nations and are seeing a significant enhance in use globally.
Many engineers have beforehand considered MICC cable know-how to be “old school’ but with the new research in hearth performance MICC cable system are actually proven to have far superior fireplace performances than any of the newer extra fashionable flexible fire resistant cables.
For further information, go to www.temperature-house.com